Product Description:
Condenser
To prevent high-temperature media from damaging the differential pressure transmitter, a condenser should be installed on the pressure transmitting tube between the throttling device and the differential pressure transmitter to protect the transmitter.
(1) Models and Applicable Range
| Model | Applicable Range |
|---|---|
| FL-6.4 | Pressure ≤6.4 MPa |
| FL-10 | Pressure ≤10.0 MPa |
| FL-20 | Pressure ≤20.0 MPa |
| FL-30 | Pressure ≤30.0 MPa |
(2) Structural Form: (As shown in the right figure)
Isolator
To prevent corrosive media from damaging the differential pressure transmitter, an isolator should be installed on the pressure transmitting tube between the throttling device and the differential pressure transmitter to protect the transmitter.
-
When the medium density is greater than the isolating liquid density, use FG-A type.
-
When the medium density is less than the isolating liquid density, use FG-B type.
(1) Models and Applicable Range
| Model | Applicable Range |
|---|---|
| FG-6.4A | Pressure ≤6.4 MPa |
| FG-10A | Pressure ≤10.0 MPa |
| FL-6.4B | Pressure ≤6.4 MPa |
| FL-10B | Pressure ≤10.0 MPa |
(2) Structural Form: (As shown in the right figure)
Gas Collector and Settler
-
When the measured medium is liquid, to prevent gas from being present in the pressure transmitting tube and affecting measurement, a gas collector is generally installed at the highest point of the pressure transmitting tube to periodically discharge gas from the tube and improve measurement accuracy.
-
When the measured medium is gas, to prevent liquid from being present in the pressure transmitting tube and affecting measurement, a settler is generally installed at the lowest point of the pressure transmitting tube to periodically discharge liquid from the tube and improve measurement accuracy.
(1) Models and Applicable Range
| Model | Applicable Range |
|---|---|
| FJ-6.4 | Pressure ≤6.4 MPa |
| FJ-10 | Pressure ≤10.0 MPa |
| FC-6.4 | Pressure ≤6.4 MPa |
| FC-10 | Pressure ≤10.0 MPa |
(2) Structural Form: (As shown in the right figure)
Balancer
-
A single-layer balancer is used when measuring the liquid level of open containers or low-pressure vessels.
-
A double-layer balancer is used when measuring the water level in a boiler drum.
(1) Models and Applicable Range
| Model | Name | Applicable Range |
|---|---|---|
| FP6.4A | Single-layer Balancer | Pressure ≤6.4 MPa |
| FP-20A | Single-layer Balancer | Pressure ≤20.0 MPa |
| FP-32B | Single-layer Balancer | Pressure ≤32.0 MPa |
| FP-6.4B | Double-layer Balancer | Pressure ≤6.4 MPa |
| FP-25B | Double-layer Balancer | Pressure ≤25.0 MPa |