Product Description
I. Instrument Types
-
SWP-W — AC Power Meter
-
SWP-HZ — AC Frequency Meter
-
SWP-AC — AC Voltage/Current Meter
-
SWP-COS — AC Power Factor Meter
-
SWP-E — AC Power Integrated Display & Control Meter
-
SWP-DC — DC Voltage/Current Meter
II. Main Features
-
Input signal ranges can be adjusted freely. Adopting jumper-free technology, users only need to configure internal parameters to meet field requirements.
-
Supports one channel of analog transmission output or relay alarm output, suitable for various measurement and control applications.
-
Full isolation technology ensures signal safety and reliability.
-
The SWP-E series meters are capable of displaying 4 groups of AC electrical parameters simultaneously.
III. Instrument Dimensions & Wiring (Basic configurations, special orders refer to the supplied wiring diagram)
-
Model: SWP-W, AC/DC, COS, HZ40 series
-
Dimensions: 96×48×110mm (cutout: 92×44mm), Weight: 240g
-
Dimensions: 48×96×110mm (cutout: 44×92mm), Weight: 240g
-
-
Model: SWP-W, AC/DC, COS, HZ80 series
-
Dimensions: 160×80×140mm (cutout: 152×76mm), Weight: 400g
-
Dimensions: 80×160×140mm (cutout: 76×152mm), Weight: 400g
-
-
Model: SWP-E80 series
-
Dimensions: 160×80×140mm (cutout: 152×76mm), Weight: 400g
-
Dimensions: 80×160×140mm (cutout: 76×152mm), Weight: 400g
-
-
Model: SWP-W, AC/DC, COS, HZ90 series
-
Dimensions: 96×96×140mm (cutout: 92×92mm), Weight: 400g
-
IV. Model Coding Table — SWP-LED AC Power Integrated Display & Control Meter
-
SWP-E: AC Power Integrated Display & Control Meter (80 series only)
-
SWP-W: AC Power Meter
-
SWP-AC: AC Voltage/Current Meter
-
SWP-COS: AC Power Factor Meter
-
SWP-HZ: AC Frequency Meter
-
SWP-DC: DC Voltage/Current Meter
Appearance Code
-
C: Horizontal display
-
S: Vertical display
Dimensions Code
-
4: 96×48mm (Horizontal) / 48×96mm (Vertical)
-
8: 160×80mm (Horizontal) / 80×160mm (Vertical)
-
9: 96×96mm
Control Function
-
01: Measurement & Display
-
03: 3-position Control
Communication Options
-
0: None
-
2: RS-232
-
4: RS-422
-
8: RS-485
Output Options
Refer to “Transmission Output Options”
Input Types
Refer to “Input Type Table”
Alarm Options
Refer to “Alarm Output Options”
Auxiliary Power Output
-
P: DC24V Auxiliary Power
Power Supply
-
W: DC24V Supply
-
T: AC90–265V Switching Power Supply
-
AC220V Linear Power Supply (default, optional omission)
Note: Instruments with dimension codes 4 and 9 cannot simultaneously support both upper/lower limit alarms and transmission output.
Example: If upper/lower limit alarms are enabled, transmission output cannot be configured. If transmission output is enabled, only one upper limit alarm is allowed.
Factory Defaults
-
SWP-W AC Power Meter: Standard dual-display
-
Input Types (default values):
| Code | Input Range | Code | Input Range | Code | Input Range | Code | Input Range |
|---|---|---|---|---|---|---|---|
| 01 | 0–1A | 04 | 0–4A | 07 | 0–200V | 10 | 0–500V |
| 02 | 0–2A | 05 | 0–5A | 08 | 0–300V | 11 | 0–600V |
| 03 | 0–3A | 06 | 0–100V | 09 | 0–400V |
⚠ Note: The maximum AC voltage input is 600V. For input voltages exceeding 600V, an external transformer must be connected.
Transmission Output Options
| Code | Output Type |
|---|---|
| 0 | None |
| 2 | 4–20mA |
| 3 | 0–10mA |
| 4 | 1–5V |
| 5 | 0–5V |
| 8 | Special Spec |
Alarm Options
| Code | Alarm Type |
|---|---|
| N | None (default) |
| H | Upper Limit Alarm |
| L | Lower Limit Alarm |
Example Models
-
SWP-EC-801-02-05-N
-
AC Power Integrated Display Meter, input: 0–5A, no communication, 4–20mA output, no alarm output.
-
-
SWP-AC-C903-81-05-H-P
-
AC Voltage Meter, input: 0–5A, relay control output, RS-485 communication, upper limit alarm, DC24V auxiliary power.
-